Enter the lock code (usually or 001 depending on the firmware) using the arrow keys, then press SET to access the parameter menu.
Based on the review of the XM TD-2201 manual, we recommend: xmtd-2201 manual
72 x 72 x 100mm (Panel size) with a 68 x 68mm cutout. Enter the lock code (usually or 001 depending
| Parameter | Name | Default | Description & Your Action | | :--- | :--- | :--- | :--- | | | Sensor Input Type | Varies | 0=K, 1=J, 2=E, 3=T, 4=S, 5=Pt100. Set to match your probe. | | S-H | High Limit | 400°C | Maximum allowed setpoint. | | S-L | Low Limit | -50°C | Minimum allowed setpoint. | | OP-A | Output Mode | 0 | 0 = Heating (Reverse action). 1 = Cooling (Direct action). | | P | Proportional Band | 30 | 1-999. Lower = aggressive heating. For ovens, start at 50. | | I | Integral Time | 240 sec | 1-3600. Removes steady-state error. Lower = faster, but unstable. | | D | Derivative Time | 60 sec | 0-999. Anticipates changes. Set to 0 for slow systems. | | T | Cycle Time | 20 sec | 1-100 sec. For relay output, use 15-20. For SSR, use 2-4. | | AL-1 | Alarm 1 Value | 10 | °C above SV. Set to 5 for limit alarm. | | HY-1 | Alarm Hysteresis | 2 | Prevents relay chatter. | | LOC | Lock Code | 0 | 0=Unlocked. 1=Semi-locked. 2=Fully locked. | Set to match your probe
Proper wiring is critical for safety and accuracy. Always disconnect power before handling terminals.